Kohler (MPAC 1500) - протоколирование данных. Карта регистров MODBUS.


Данные ниже соответствуют только программе Advanced Serial Data Logger или Advanced TCP/IP Data Logger и могут быть не применимы для других программных продуктов.

Смещение MODBUSОписаниеЕд. изм.Тип данных
1Source N line neutral l1l0Volts ACword
2Source N line neutral L2 l0Volts ACword
3Source N line neutral l3l0Volts ACword
4Source E line neutral L1 l0Volts ACword
5Source E lineneutral l2l0Volts ACword
6Source E line neutral L3 l0Volts ACword
7Source N line напряжение L1 L2Volts ACword
8Source N line напряжение L2 L3Volts ACword
9Source N line напряжение L3 L1Volts ACword
10Source E line напряжение L1 L2Volts ACword
11Source E line напряжение l2l3Volts ACword
12Source E line напряжение L3 L1Volts ACword
13Source N частотаHzword
14Source E частотаHzword
15Ток L1Ampsword
16Ток L2Ampsword
17Ток L3Ampsword
18Closed transition in фаза degree deltaDegreesword
38Closed programmed transition override mode0 = Auto Override, 1 = Non-Automaticword
39Password for writing register 400420-32768word
40Synchronous напряжение фазовый угол0-10 degreesword
41Synchronous напряжение differential0%-5%word
42Synchronous частота differential0.0Hz.-0.3Hz.word
43Service entrance type0 = None; 1 = Insulated Case Circuit Breaker, 2 = Molded Case Circuit Breaker, 3 = Contactorword
44Фаза rotation actual0 = disabled; 1 = ABC; 2 = CBAword
45Фаза rotation expected0 = disabled; 1 = ABC; 2 = CBAword
46Nominal normal напряжениеVolts ACword
47Nominal emergency напряжениеVolts ACword
48Nominal normal частотаHzword
49Nominal emergency частотаHzword
50Normal number of фазаs1 or 3word
51Emergency number of фазаs1 or 3word
52Rated amperage04000word
57Password for writing register 400570 32768word
58Normal engine start time delay0-10 secword
59Emergency engine start time delay010 secword
60Normal ext. Engine start time delay0-3600 secword
61Emergency ext. Engine start time delay03600 secword
62Normal engine cooldown0-3600 secword
63Emergency engine cooldown03600 secword
64Standby to preferred0-3600 secword
65Preferred to standby03600 secword
66Off (preferred to standby prog. Transition)0-3600 secword
67Off (standby to preferred prog. Transition)03600 secword
68Fail to acquire preferred1 -3600 secword
69Fail to acquire standby13600 secword
70Fail to synchronize1 -3600 secword
71Fail to synch. Enable0 = disabled; 1 = enabledword
74Активная time delay word
75Активная time delay remainingSecondsword
Есть еще ряд значений MODBUS для этого устройства. Их можно посмотреть в программе.