Смещение MODBUS | Описание | Ед. изм. | Тип данных |
1 | Sourcea line neutral L1 l0 | Volts AC | word |
2 | Sourcea line neutral L2 l0 | Volts AC | word |
3 | Sourcea line neutral L3 l0 | Volts AC | word |
4 | Sourceb line neutral L1 l0 | Volts AC | word |
5 | Sourceb line neutral L2 l0 | Volts AC | word |
6 | Sourceb line neutral L3 l0 | Volts AC | word |
7 | Sourcea line напряжение L1 L2 | Volts AC | word |
8 | Sourcea line напряжение L2 L3 | Volts AC | word |
9 | Sourcea line напряжение L3 L1 | Volts AC | word |
10 | Sourceb line напряжение L1 L2 | Volts AC | word |
11 | Sourceb line напряжение L2 L3 | Volts AC | word |
12 | Sourceb line напряжение L3 L1 | Volts AC | word |
13 | Sourcea частота | Hz | word |
14 | Sourceb частота | Hz | word |
23 | Sourcea nominal напряжение | Volts AC | word |
24 | Sourceb nominal напряжение | Volts AC | word |
25 | Sourcea nominal частота | Hz | word |
26 | Sourceb nominal частота | Hz | word |
27 | Sourcea number of фазаs | 1 or 3 | word |
28 | Sourceb number of фазаs | 1 or 3 | word |
29 | Rated amperage | 0-4000 | word |
31 | Sourcea engine start time delay (id 0x0001) | 0-6 sec | word |
32 | Sourceb engine start time delay (id 0x0002) | 0-6 sec | word |
33 | Sourcea ext engine start time delay (id 0x0003) | 0-5999 sec | word |
34 | Sourceb ext engine start time delay (id 0x0004) | 0-5999 sec | word |
35 | Sourcea engine cooldown time delay (id 0x0005) | 0-5999 sec | word |
36 | Sourceb engine cooldown time delay (id 0x0006) | 0-5999 sec | word |
37 | Preferred to standby time delay (id 0x0007) | 0-5999 sec | word |
38 | Standby to preferred time delay (id 0x0008) | 0-5999 sec | word |
39 | Off to preferred time delay (id 0x0009) | 0-5999.9 sec | word |
40 | Off to standby time delay (id 0x000a) | 0-5999.9 sec | word |
41 | Acquire standby source (id 0x000b) | 1-5999 sec | word |
42 | Inфаза monitor synch (id 0x000c) | 1-5999 sec | word |
44 | Sourcea over volt dropout trip point | 105 - 135) % of rated source voltage | word |
45 | Sourcea over volt pickup trip point | 95 - 100)% of over voltage dropout point | word |
46 | Sourcea under volt pickup trip point | 85 - 100) % of rated source voltage | word |
47 | Sourcea under volt dropout trip point | 75 - 98) % of overvoltage pickup point | word |
48 | Sourcea напряжение debounce time | Sec | word |
49 | Sourceb over volt dropout trip point | 105 - 135) % of rated source voltage | word |
50 | Sourceb over volt pickup trip point | 95 - 100)% of over voltage dropout point | word |
51 | Sourceb under volt pickup trip point | 85 - 100) % of rated source voltage | word |
52 | Sourceb under volt dropout trip point | 75 - 98) % of overvoltage pickup point | word |
53 | Sourceb напряжение debounce time | Sec | word |
54 | Sourcea over freq dropout trip point | 101 -105) % of overfreq pickup point | word |
55 | Sourcea over freq pickup trip point | 105 - 120) % of rated source freq | word |
56 | Sourcea under freq dropout trip point | 95 - 99) % of underfreq pickup point | word |
57 | Sourcea under freq pickup trip point | 80 - 95)% of rated system frequency | word |
58 | Sourcea freq dropout time | Sec | word |
59 | Sourceb over freq dropout trip point | 101 -105) % of overfreq pickup point | word |
60 | Sourceb over freq pickup trip point | 105 - 120) % of rated source freq | word |
61 | Sourceb under freq dropout trip point | 95 - 99) % of underfreq pickup point | word |
62 | Sourceb under freq pickup trip point | 80 - 95)% of rated system frequency | word |
63 | Sourceb freq dropout time | Sec | word |
64 | Ats controller выход | Event Code | word |
65 | I/o module 1 выход 1 | Event Code | word |
66 | I/o module 1 выход 2 | Event Code | word |
67 | I/o module 1 выход 3 | Event Code | word |
68 | I/o module 1 выход 4 | Event Code | word |
69 | I/o module 1 выход 5 | Event Code | word |
70 | I/o module 1 выход 6 | Event Code | word |
71 | I/o module 2 выход 1 | Event Code | word |
72 | I/o module 2 выход 2 | Event Code | word |
73 | I/o module 2 выход 3 | Event Code | word |
74 | I/o module 2 выход 4 | Event Code | word |
75 | I/o module 2 выход 5 | Event Code | word |
76 | I/o module 2 выход 6 | Event Code | word |
77 | I/o module 3 выход 1 | Event Code | word |
78 | I/o module 3 выход 2 | Event Code | word |
79 | I/o module 3 выход 3 | Event Code | word |
80 | I/o module 3 выход 4 | Event Code | word |
81 | I/o module 3 выход 5 | Event Code | word |
82 | I/o module 3 выход 6 | Event Code | word |
83 | I/o module 4 выход 1 | Event Code | word |
84 | I/o module 4 выход 2 | Event Code | word |
85 | I/o module 4 выход 3 | Event Code | word |
86 | I/o module 4 выход 4 | Event Code | word |
87 | I/o module 4 выход 5 | Event Code | word |
88 | I/o module 4 выход 6 | Event Code | word |
89 | Tsi1 event | Event Code | word |
90 | Tsi2 event | Event Code | word |
91 | I/o module 1 вход 1 | Event Code | word |
92 | I/o module 1 вход 2 | Event Code | word |
93 | I/o module 2 вход 1 | Event Code | word |
94 | I/o module 2 вход 2 | Event Code | word |
95 | I/o module 3 вход 1 | Event Code | word |
96 | I/o module 3 вход 2 | Event Code | word |
97 | I/o module 4 вход 1 | Event Code | word |
98 | I/o module 4 вход 2 | Event Code | word |