Elspec (G4400) логгер. Карта регистров MODBUS.


Данные ниже соответствуют только программе Advanced Serial Data Logger или Advanced TCP/IP Data Logger и могут быть не применимы для других программных продуктов.

Смещение MODBUSОписаниеЕд. изм.Тип данных
543Compliance name (EN 50160 or any other compliance standard)Stringstring
563Compliance descriptionStringstring
603OK / fail / NA status of the compliance токly runningUINT16word
621Percentage from the entire time (including off time) in which this compliance parameters was okfloatsingle
623Percentage from the entire time (including off time) in which this the compliance parameter was not okfloatsingle
625Percentage from the entire time (including off time) in which this compliance parameter was not evaluated (due to device off time)floatsingle
627Number of compliance parameters under checkUINT32dword
537Мощность supply temperature (read every second)floatsingle
999The measured частота , calculated every 200 msec (10/12 cycles)floatsingle
1025Line 1 активная мощность (W), calculate every cyclefloatsingle
1027Line 2 активная мощность (W), calculate every cyclefloatsingle
1029Line 3 активная мощность (W), calculate every cyclefloatsingle
1037Сумма активная мощность (W), calculate every cyclefloatsingle
1041Line 1 реактивная мощность (VAr) calculate every cyclefloatsingle
1043Line 2 реактивная мощность (VAr) calculate every cyclefloatsingle
1045Line 3 реактивная мощность (VAr) calculate every cyclefloatsingle
1053Реактивная мощность - сумма (VAr) calculate every cyclefloatsingle
1057Line 1 кажущаяся мощность (VA) calculate every cyclefloatsingle
1059Line 2 кажущаяся мощность (VA) calculate every cyclefloatsingle
1061Line 3 кажущаяся мощность (VA) calculate every cyclefloatsingle
1069Кажущаяся мощность сумма (VA) calculate every cyclefloatsingle
1103RMS напряжение V1, calculate every cyclefloatsingle
1105RMS напряжение V2, calculate every cyclefloatsingle
1107RMS напряжение V3, calculate every cyclefloatsingle
1109RMS напряжение V12, calculate every cyclefloatsingle
1111RMS напряжение V23, calculate every cyclefloatsingle
1113RMS напряжение V31, calculate every cyclefloatsingle
1117RMS напряжение I1, calculate every cyclefloatsingle
1119RMS напряжение I2, calculate every cyclefloatsingle
1121RMS ток I3, calculate every cyclefloatsingle
1123Cycle by cycle average RMS напряжениеfloatsingle
1125Cycle by cycle average RMS фаза to фаза напряжениеfloatsingle
1127Cycle by cycle average RMS токfloatsingle
1159Internal DSP temperature, read every cyclefloatsingle
1161External DSP temperature (PT100 READING) , read every cyclefloatsingle
1659PST (short term flicker) - L1 - calculated over 2 secondsfloatsingle
1661PST (short term flicker) - L1 - calculated over 2 secondsfloatsingle
1663PST (short term flicker) - L1 - calculated over 2 secondsfloatsingle
1665PST (short term flicker)- L12 - calculated over 2 secondsfloatsingle
1667PST (short term flicker)- L23 -calculated over 2 secondsfloatsingle
1669PST (short term flicker)- L31 - calculated over 2 secondsfloatsingle
1671PST (short term flicker) - L1 - calculated over 10 secondsfloatsingle
1673PST (short term flicker)- L2 - calculated over 10 secondsfloatsingle
1675PST (short term flicker)- L3 - calculated over 10 secondsfloatsingle
1677PST (short term flicker)- L12 - calculated over 10 secondsfloatsingle
1679PST (short term flicker)- L23 - calculated over 10 secondsfloatsingle
1681PST (short term flicker)- L31 - calculated over 10 secondsfloatsingle
1683PST (short term flicker)- L1 - calculated over 10 minutesfloatsingle
1685PST (short term flicker)- L2 - calculated over 10 minutesfloatsingle
1687PST (short term flicker)- L3 - calculated over 10 minutesfloatsingle
Есть еще ряд значений MODBUS для этого устройства. Их можно посмотреть в программе.

Замечание: Продукты и компании, указанные здесь используются только для обозначение и идентификации и могут быть торговыми и/или зарегистрированными марками соответствующих компаний.